Low GWP Rrefrigerants r1234ze(e) and r1234ze(z) for High Temperature Gound Source Heat Pumps

This project is designed for Food Processing Plant in Southeast Asia, which is used to provide maximum 75℃ hot water to the machine on the food processing process.
According to actual need of customer, this project was advised to use R1234ze refrigerant as medium to achieve maximum 75℃ hot water. It’s low gwp refrigerants r1234ze(e) and r1234ze(z) for high temperature heat pumps.

Inquiry now
Product Detail

Low GWP Refrigerants r1234ze(e) and r1234ze(z) for High Temperature Gound Source Heat Pumps


Heat Pump Features Overview

High temperature ground source heat pump with high COP
Environmentally friendly refrigerant with super low GWP – R1234ZE.
Special design high temperature semi-hermetic screw type compressor.
Condenser maximum water outlet temperature 75oC.
Evaporator water inlet temperature range 27oC - 45oC.
Compressor part load from 0%, 50%, 75%, 100% based on hot water requirement during peak and non-peak.
Multiple safety protections.
Drier-filter inspection sight-glass for visible refrigeration state.
Built-in control cabinet attuned to all components and requirements.
Control based on PLC, integration of pumps, valves, fans, etc.
Reliable electromagnetic expansion valve for optimal and precise refrigerant injection in the evaporator.  
Electronic PLC controller (monitoring running parameter digitally)
Graphic touch screen
Clear text fault messages in case of malfunctions  
Graphic display of refrigeration circuit diagram and components
Refrigeration temperature monitoring
Operation point
Application limits 

High level interfacing connectivity to external energy monitoring panel or BMS


Specification

DESCRIPTION

40STD-790WHS4 (Customized)

TECHNICAL DATA

*Nominal Heating Capacity, kW

752.8

*Nominal Cooling Capacity, kW

620

COP

5.67

Rated Input Power, kW

132.8

Power Supply, Volts/Ph/Hz

415/3/50

Refrigerant

R1234ZE

Refrigerant Factory Charge, kg

134

Rated Outlet Water Temperature, °C

55

Max. Outlet Water Temperature, °C

75

Dimensions (L x W x H), mm

3900x1800x2200

Noise Level, dB

82

Safety Protection

Phase Reversion, Phase Loss, Overload Current, Low/High Pressure, Low Temp, Low Water Flow, High Discharge Temp

Metering Device

Electronic Expansion Valve

Net Wt./Approx. Shipping Wt., kg

3000

Testing

Run Tested at Factory Prior to Shipment

COMPRESSOR

Quantity/Type

1/Semi-Hermetic Screw Type

Volts/Phase/Hertz

415/3/50

Rated Load Amps, A

227A 

Capacity Control

0%, 50%, 75%, 100%

EVAPORATOR

Heat Exchanger Type

Shell & Tube (Copper Tube, Steel Shell)

Cooling Side Water Flow Rate, m3/hr

47.27

Pressure Drop thru Heat Exchanger, kPa

53

Max. Working Pressure (Water Side), kPa

1000

Water Connection

DN125

CONDENSER

Heat Exchanger Type

Shell & Tube (Copper Tube, Steel Shell)

Heating Side Water Flow Rate, m3/hr

129.67

Pressure Drop thru Heat Exchanger, kPa

61

Max. Working Pressure (Water Side), kPa

1000

Water Connection

DN125

Rated condition: Source inlet/outlet water temperature38oC/27oC, condenser inlet/outlet water temperature 50oC/55oC.

R1234ZE Refrigerant
Summary
R1234ze is a low Global Warming Potential (GWP) refrigerant, The R1234ze refrigerant is a HFO refrigerant , used as a replacement for R134a in medium temperature refrigeration and air conditioning applications including water chillers.

R1234ZE Refrigerant Application


Advantage: 
1. The R1234ze refrigerant is a HFO refrigerant with a very low GWP (7). vs 1300 of the R134a 
Disadvantage: 
1. the R1234ze chiller compressor is larger in size and operates at a lower speed (rpm) for the same chiller capacity

215 Ton Heat Pump Unit Design

215 Ton Heat Pump Unit Design



H.Stars Heat Pump Production Photos


 ground source heat pumphigh temperature ground source heat pumplow gwp refrigerants r1234ze(e) and r1234ze(z) for high temperature heat pumps




contact experts
Contact Person: Ms May Chow Mobile/WhatsApp: +86 18665672648 Tel: +86-20-62266755 Ext. 886 Fax: +86-20-82266081 Email: maychow@hstars.com.cn
Related Products
Modular water source heat pump unit Modular Water Source Heat Pump Unit
"H'Stars" modular water source heat pump unit can be used for refrigeration and heating, and can be replaced by one machine. The system can replace the original boiler and air conditioning system; the cooling capacity is sufficient, the efficiency is high, the cleaning and maintenance is easy, and the energy efficiency rating is 5-1. level.
Flooded and screw type heat pump Flooded And Screw Type Water Source Heat Pump Unit
"H'Stars" 40STD series Flooded and screw type water source heat pump unit adopts high-efficiency twin-screw compressor, self-developed and manufactured high-efficiency Flooded type evaporator, R22, R134a refrigerant, energy efficiency up to 6.7. Hot water outlet temperature 50 °C . The heat recovery unit can be configured according to customer requirements. The unit has a total of 20 standard specifications.
Water Source Heat Pump Unit Heat Recovery Screw Type Water Source Heat Pump Unit
“H'Stars” heat recovery screw-type water source heat pump unit uses the chiller to exchange heat between the refrigerant vapor and water during operation, converting the energy-consuming heat into usable hot water, and providing a large amount of air-conditioning while providing air-conditioning. Hot water in life.
hot water chiller hot water chiller with cold recovery
Hot water chiller(cold recovery) is using the air as low heat source to produce the heat water. Energy saving, high efficiency and environmental protection, the waste cold discharged in the heating process is recovered through the cold recovery device, to improve the comprehensive energy efficiency and realize zero cost refrigeration
 Sewage water source heat pump unit 55℃ Sewage Source Heat Pump Unit
H'Stars Sewage source heat pump unit(with cold/heat recovery) is a hot water equipment developed and produced for Bathhouse, Hot spring pool, Swimming pool and other bathing places, extracting the heat from domestic sewage, saving energy and protecting the environment.Energy saving is 30%~50% compared with conventional heating method, which can greatly reduce the operation cost.
heat pump with cooling system heat pump with cooling system
heat pump with cooling Introduction: The cold recovery intelligent hot water unit uses air as the low-level heat source to produce hot water, which is energy-efficient, environmentally friendly, and recycles waste cold discharged during the heating process through a cold recovery unit to improve overall energy efficiency and achieve zero-cost refrigeration. Brand: Hstars Heat capacity range: 25kw-70kw Applications: Applications: factories, hospitals, printing plants, etc.

Copyright © 2015-2024 H.Stars (Guangzhou) Refrigerating Equipment Group Ltd.

/ Blog / Sitemap / XML
  • 1
  • Linkedin
  • twitter
  • instagram
  • youtube
welcome to H.Stars

Home

Products

about