Combined cooling and heating system tri-function chiller
Cooling/hot water mode
When turned on, the combined cooling and heating system chiller is in the cooling/hot water mode, which produces free domestic hot water during the cooling process; when the air conditioning chilled water reaches its set value but the domestic hot water does not,the system will automatically switch to hot water mode;when the domestic hot water reaches its set value, but the air conditioning chilled water does not, the system will automatically switch to cooling water mode; and when both air conditioning chilled water and domestic hot water reach their own set value, the compressor stops and the system enters into the standby mode .
Heating/hot water mode
Winter heating-hot water mode 1 (with priority on hot water): When turned on, the system will go into hot water mode, and when the hot water temperature reaches its set value, the system will automatically switch to heating mode; when the hot water temperature drops below the set value again, the system
will switch back into hot water mode again; and when both hot water and floor heating temperatures reach their respective set values, the compressor stops and the system enters into the standby mode. Winter heating-hot water mode 2 (with priority on heating): When turned on, the system will go into heating mode, and when the heating reaches its set value, the system will automatically switch to hot water mode; when the heating temperature drops below the set value again, the system will switch back into heating mode; and when both hot water and floor heating temperatures reach their respective set values, the compressor stops and the system enters into the standby mode.
Hot water mode
The system will run the mode of producing domestic hot water; when the hot water temperature reaches the set value, the compressor stops and the system enters into the standby mode; and when the hot water drops below the set value again, the system will automatically start to produce hot water.
Heating mode
The system will run the heating mode; when the floor heating temperature reaches the set value, the compressor stops and the system enters into the standby mode; and when the heating temperature drops below the set value again, the system will automatically start the heating process.
Cooling mode
The system will run the cooling mode; when the cooling temperature reaches the set value, the compressor stops and the system enters into the standby mode; and when the chilled water temperature rises above the set value again, the system will automatically start the cooling process. (To avoid frequent switches between modes, cooling mode can be selected in summer, when hot water is not needed)Specification:
Technical Parameter Table of H.Stars Scroll Tri-function Systems
Refrigerant: R134a Power supply: 380V-3Ph-50Hz
Model |
Nominal cooling |
Nominal hot water |
Floor heating |
Chilled water |
Hot water |
Heat exchanger |
Axial fan |
Running noise B(A) |
Shipping weight kg |
Running weight kg |
|||||||||
Cooling capacity KW |
Compressor input power KW |
Heating capacity KW |
Compressor input power KW |
Heating capacity KW |
Compressor input popup KW |
Diameter of inlet and outlet pipes in |
Water flow rate m³/h |
Water pressure drop kPa |
Diameter of inlet and outlet pipes in |
Water flow rate m³/h |
Water pressure drop kPa |
water side |
Air side |
Air flow rate *1000 m³/h |
Input power KW* Qty |
||||
30ST-M10AS4 |
17 |
5 |
26 |
7 |
18 |
5 |
1-1/2’ |
4 |
23 |
1-1/2’ |
4 |
23 |
Shell and tube type |
Hydrophilic corrugated aluminum with copper pipe sleeve |
14.5 |
1.2*1 |
65 |
620 |
730 |
30ST-M12.5AS4 |
21 |
7 |
32 |
8 |
22 |
7 |
2’ |
5 |
28 |
2’ |
6 |
28 |
14.5 |
1.2*1 |
66 |
680 |
790 |
||
30ST-M15AS4 |
26 |
8 |
39 |
10 |
27 |
8 |
2’ |
6 |
30 |
2’ |
7 |
30 |
20 |
2.0*1 |
67 |
830 |
940 |
||
30ST-M20AD4 |
34 |
10 |
52 |
14 |
36 |
10 |
2’ |
7 |
28 |
2’ |
9 |
28 |
29 |
1.2*2 |
67 |
980 |
1090 |
||
30ST-M25AD4 |
42 |
14 |
64 |
16 |
44 |
14 |
2’ |
9 |
28 |
2’ |
11 |
28 |
29 |
1.2*2 |
68 |
1030 |
1140 |
||
30ST-M30AD4 |
52 |
16 |
78 |
20 |
54 |
16 |
2-1/2’ |
11 |
32 |
2-1/2’ |
13 |
32 |
40 |
2.0*2 |
69 |
1280 |
1390 |
Notes:
1. Nominal cooling capacity: ambient dry/wet bulb temperature 35℃ /24℃ , and temperature of inlet/outlet air-conditioning chilled water 12℃ /7℃ ;
2. Floor heating capacity: ambient dry/wet bulb temperature 7℃ /6℃ , and temperature of inlet/outlet air-conditioning hot water 40℃ /45℃ ;
3. Nominal hot water capacity: ambient dry/wet bulb temperature 20℃ /15℃ , and temperature of inlet/outlet domestic hot water 50℃ /55℃ ;
4. Cooling ambient temperature range: 15 ~ 43℃ ; heating ambient temperature range: -10 ~ 43℃ , and fouling coefficient 0.088m ² •℃ /kW;
5. Optional voltages: 220V, 380V, 400V, 415V, 440V, 460V
6. Specifications and dimensions are subject to change due to product improvement without prior notice
Technical Parameter Table of H.Stars Screw Tri-function Systems
Refrigerant: R134a Power supply: 380V-3Ph-50Hz
Model |
Nominal cooling |
Nominal hot water |
Floor heating |
Chilled water |
Hot water |
Heat exchanger |
Axial fan |
Running noise B(A) |
Shipping weight kg |
Running weight kg |
|||||||||
Cooling capacity KW |
Compressor input power KW |
Heating capacity KW |
Compressor input power KW |
Heating capacity KW |
Compressor input popup KW |
Diameter of inlet and outlet pipes in |
Water flow rate m³/h |
Water pressure drop kPa |
Diameter of inlet and outlet pipes in |
Water flow rate m³/h |
Water pressure drop kPa |
water side |
Air side |
Air flow rate *1000 m³/h |
Input power KW* Qty |
||||
60ST-M190AS4 |
75 |
23 |
110 |
29 |
78 |
22 |
2-1/2’ |
16 |
26 |
1-1/2’ |
19 |
26 |
Shell and tube type |
Hydrophilic corrugated aluminum with copper pipe sleeve |
57 |
1.2*4 |
74 |
1730 |
1880 |
60ST-M270AS4 |
107 |
32 |
156 |
41 |
111 |
31 |
3’ |
23 |
32 |
2’ |
27 |
32 |
80 |
2.0*4 |
78 |
2200 |
2450 |
||
60ST-M360AS4 |
143 |
43 |
208 |
54 |
147 |
41 |
3’ |
31 |
35 |
2’ |
36 |
35 |
114 |
1.2*8 |
79 |
3190 |
3470 |
||
60ST-M420AS4 |
169 |
49 |
244 |
62 |
173 |
47 |
3’ |
36 |
50 |
2’ |
42 |
50 |
115 |
1.2*8 |
80 |
3560 |
3940 |
||
60ST-M480AS4 |
195 |
56 |
282 |
71 |
199 |
54 |
4’ |
42 |
55 |
4’ |
49 |
55 |
115 |
1.2*8 |
80 |
3750 |
4170 |
||
60ST-M520AS4 |
217 |
60 |
311 |
77 |
220 |
59 |
4’ |
47 |
58 |
4’ |
53 |
58 |
161 |
2.0*8 |
82 |
3920 |
4250 |
||
60ST-M580AS4 |
236 |
68 |
341 |
86 |
241 |
66 |
4’ |
51 |
64 |
4’ |
59 |
64 |
161 |
2.0*8 |
83 |
4040 |
4430 |
Product photos: