Low Temperature Shell and Tube Flooded Type Evaporator
1. Flooded evaporators are the efficient heat exchanger developed in the air-conditioning and refrigeration industries.
Flooded evaporator simplified graph:
Flooded type evaporator technical parameters:
Model
Heat Exchange Capacity(KW)
Chilled Water In/outlet (inch)
Refrigerant Inlet(inch)
Refrigerant Outlet(inch)
Length A(mm)
Width B(mm)
Height C(mm)
Weight(kg)
R22
R134a
R407C
UCM100A
352
281
317
4"
1-1/8",1-3/8"
4"
2837
617
711
617
UCM150A
528
422
475
5"
1-1/8",1-3/8"
5"
3446
666
781
778
UCM200A
703
563
633
5"
2-1/8",1-3/8"
5"
3446
760
845
798
UCM250A
879
703
791
6"
2-1/8",2-1/8"
5"
3946
760
845
910
UCM300A
1055
844
950
6"
2-1/8",1-5/8"
4"
3992
718
900
1299
UCM400A
1407
1125
1266
6"
2-1/8",1-5/8"
4"
3992
718
900
1391
Advantages, Features and Application
1. Adopt 1.1mm thickness special heat exchange tube, T-shaped heat exchange tube greatly increases the heat transfer area.
2. The tube side is designed as 3 systems, increasing the flow rate of refrigerant to improve the heat transfer efficiency.
3. Adapt to compressors such as screw, centrifugal and magnetic type. The difference between the effluent temperature and the evaporation temperature approaches and low resistance.
4. High performance self-made ASME heat exchanger evaporator from raw material metal sheet, strict quality control and pretty competitive price.
5. X-ray Leakage test, Water Bath Leakage Test, N2 Pressure Test with third party certification for each heat exchanger before shipment.
6. All associated parts including covers, tube sheet, eliminator, flanges, sensor wells, are all made within the production line.